After working for a week now heatpumpmonitor crashes after an hour
This bug report was converted into a question: question #184399: After working for a week now heatpumpmonitor crashes after an hour.
Affects | Status | Importance | Assigned to | Milestone | |
---|---|---|---|---|---|
heatpumpMonitor |
Invalid
|
Undecided
|
Unassigned |
Bug Description
Hi,
I set up heatpumpmonitor on a Mac Mini, connected to a Tecalor 403SOL running 4.39. For a week everything worked, now suddenly heatpumpmonitor crashes after an hour:
Starting ...
========= Tue Jan 10 08:30:44 2012 =========
Error: the received getVersion response has an invalid length (53 instead of 2)
---------
Traceback (most recent call last):
File "/usr/local/
p = protocol.
File "/usr/local/
self._version = self.versionQuery()
File "/usr/local/
return self._getVersion()
File "/usr/local/
return str(convert2Num
File "/usr/local/
raise IOError, "Error: the received %s response has an invalid length (%d instead of %d)" % (queryName, len(s) - 2, queryResponseLe
IOError: Error: the received getVersion response has an invalid length (53 instead of 2)
=========
Starting ...
Heatpump reports Version 4.39
Using protocol definition from Robert Penz <email address hidden> and Jack Sleuters (Tested with LWZ 303/403 Sol, send me a line if it works on others too.)
Up and running
========= Tue Jan 10 09:45:23 2012 =========
Error: the received OperationalState response has an invalid length (53 instead of 10)
---------
Traceback (most recent call last):
File "/usr/local/
values = p.query()
File "/usr/local/
result.
File "/usr/local/
s = self._get(
File "/usr/local/
raise IOError, "Error: the received %s response has an invalid length (%d instead of %d)" % (queryName, len(s) - 2, queryResponseLe
IOError: Error: the received OperationalState response has an invalid length (53 instead of 10)
=========
The only way to get it working again is to physically remove the serial cable after stopping the daemon, connect it again and restart the daemon. The graphs can be seen at wp.home.
Can you please help me figure this out? Also, it would be interesting for me to see the power consumption of my 403SOL in a graph.
Thanks in advance,
Thomas.
Hi,
it turns out that the problem was due to a faulty cable. I replaced the cable and now heatpumpMonitor is working ok.
Sorry for the confusion.
The question about the power consumption values remains: is there a possibility to add those to the graphs?
Best regards,
Thomas.